$ Sample DOE2.2 Input File Snippets $ ASHRAE 90.1-2007 PRM characterizations $ Large Office New York City, Climate Zone 4A, New York Kennedy WSO AP $--------------------------------------------------------------------------------------------------------------- $ Appendix G Envelope Constructions $ EXTERIOR WALL "R-eff wall" = MATERIAL TYPE = RESISTANCE RESISTANCE = 7.2 $ASHRAE 4A - 7.2 eff R-value for R-13 batt in 4", 24"o.c. steel frame $ Specify with parameter value - {#pa("R Stud Wall")} .. "R-ci wall" = MATERIAL TYPE = RESISTANCE RESISTANCE = 7.5 $ASHRAE 4A - 7.5 continuous insulation outside stud wall $ Specify with parameter value - {#pa("R CI Wall")} .. "ASHRAE EWall Cons Layers" = LAYERS MATERIAL = ( "GypBd 1/2in (GP01)", "Bldg Paper Felt (BP01)", "R-ci wall", "R-eff wall", "GypBd 1/2in (GP01)" ) THICKNESS = ( 0.042 ) .. $ If proposed design is not a lightweight wall, can define additional wall types "Block EWall Cons Layers" = LAYERS MATERIAL = ( "Conc HW 140lb 6in (CC04)", "Bldg Paper Felt (BP01)", "R-ci wall", "R-eff wall", "GypBd 1/2in (GP01)" ) .. "E1 EWall Construction" = CONSTRUCTION TYPE = LAYERS ABSORPTANCE = 0.6 ROUGHNESS = 1 LAYERS = "ASHRAE EWall Cons Layers" $ substitute value with parameter name - e.g. ext_wall_layers[] $ {SymIndex(#pa("Exterior Wall Layers"),"CONSTRUCTION","LAYERS")} $ ROOF "R-ci Roof" = MATERIAL TYPE = RESISTANCE RESISTANCE = 20 $ Substitute value with parameter name - e.g. {#pa("R CI Roof")} .. "Roof Cons Layers" = LAYERS MATERIAL = ( "Blt-Up Roof 3/8in (BR01)", "Bldg Paper Felt (BP01)", "Plywd 5/8in (PW04)", "R-ci Roof" ) .. "Roof Construction" = CONSTRUCTION TYPE = LAYERS ABSORPTANCE = 0.7 $ Reflectivity = 0.3; $ Substitute value with parameter name - {#pa("Roof Absorptance")} ROUGHNESS = 1 LAYERS = "Roof Cons Layers" .. $ --------------------------------------------------------- $ Glass Types $ --------------------------------------------------------- "EL1 Window Type #1 GT" = GLASS-TYPE TYPE = SHADING-COEF SHADING-COEF = {0.40 / 0.87} $ use parameter substitution {#pa("Glass SHGC") / 0.87} GLASS-CONDUCT = {1 / ((1/0.50) - 0.193)} $exclude ext film heat transfer coefficient; $use parameter substitution {1/((1/#PA("Glass U VALUE"))-0.193)} .. SET-DEFAULT FOR WINDOW GLASS-TYPE = "EL1 Window Type #1 GT" .. $--------------------------------------------------------------------------------------------------------------- $ Appendix G Chiller and Boiler Plant $ **************************************************************************** $ $ ASHRAE APP G/PRM VALUES FOR BOILER SYSTEM $ $ ***************************************************************************** $ G3.1.3.4 Hot Water Supply Temperature Reset (System 1, 5, and 7) "HW-RESET-ASHRAE-DAY" = DAY-SCHEDULE-PD TYPE = RESET-TEMP OUTSIDE-HI = 50 OUTSIDE-LO = 20 SUPPLY-HI = 180 $ need to check SUPPLY-LO = 150 $ need to check .. "HW-RESET-ASHRAE-WK" = WEEK-SCHEDULE-PD TYPE = RESET-TEMP DAY-SCHEDULES = ( "HW-RESET-ASHRAE-DAY" ) .. "HW-RESET-ASHRAE-SCH" = SCHEDULE-PD TYPE = RESET-TEMP MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "HW-RESET-ASHRAE-WK" ) .. "HW Loop Pump" = PUMP NUMBER = 1 MOTOR-CLASS = HI-EFF CAP-CTRL = VAR-SPEED-PUMP $ ONE-SPEED < 120,000 SF < VAR-SPEED .. "Hot Water Loop" = CIRCULATION-LOOP TYPE = HW LOOP-DESIGN-DT = 50 $ Design return temperature of 130 F DESIGN-HEAT-T = 180 HEAT-SETPT-CTRL = OA-RESET HEAT-RESET-SCH = HW-RESET-ASHRAE-SCH LOOP-PUMP = "HW Loop Pump" .. "BB Loop Pump" = PUMP LIKE "HW Loop Pump" .. "Baseboard Loop" = CIRCULATION-LOOP TYPE = HW LOOP-PUMP = "BB Loop Pump" LOOP-OPERATION = SCHEDULED HEATING-SCHEDULE = "BB Schedule ON/OFF" .. "Boiler-1" = BOILER $ DUAL BOILER PLANT 1 boiler < 15,000 SF < 2 boilers TYPE = HW-BOILER CAPACITY-RATIO = 0.65 $ two @ 125% of total load HEAT-INPUT-RATIO = { 1 / 0.75 } $ Define efficiency as parameter variable - {1/#pa("Boiler Eff")} HW-LOOP = "Hot Water Loop" .. "Boiler-2" = BOILER LIKE Boiler-1 .. "Baseboard Boiler-1" = BOILER LIKE Boiler-1 HW-LOOP = "Baseboard Loop" .. "Baseboard Boiler-2" = BOILER LIKE "Boiler-2" HW-LOOP = "Baseboard Loop" .. $ **************************************************************************** $ $ ASHRAE APP G/PRM DEFAULTS FOR WATER-COOLED CHILLER SYSTEM $ $ ***************************************************************************** "CW Pump 1" = PUMP CAP-CTRL = ONE-SPEED-PUMP .. "CW Pump 2" = PUMP CAP-CTRL = ONE-SPEED-PUMP .. "Condenser Water Loop" = CIRCULATION-LOOP TYPE = CW DESIGN-COOL-T = 82 $ ashrae = lesser of ( wb +10, or 85 ) COOL-SETPT-CTRL = FIXED COOL-SETPT-T = 70 LOOP-OPERATION = STANDBY .. "Cooling Tower 1" = HEAT-REJECTION TYPE = OPEN-TWR CAPACITY-RATIO = 1 NUMBER-OF-CELLS = 2 CELL-CTRL = MIN-CELLS ELEC-INPUT-RATIO = 0.013 $ BTU/BTU CAPACITY-CTRL = TWO-SPEED-FAN DESIGN-APPROACH = 10 DESIGN-WETBULB = 72 $ depends on climate, see ASHRAE 90.1 Table D-1 CW-LOOP = "Condenser Water Loop" .. $ ===================================== CHW ================================== "CHW-RESET-ASHRAE-DAY" = DAY-SCHEDULE-PD TYPE = RESET-TEMP OUTSIDE-HI = 80 OUTSIDE-LO = 60 SUPPLY-HI = 54 SUPPLY-LO = 44 .. "CHW-RESET-ASHRAE-WK" = WEEK-SCHEDULE-PD TYPE = RESET-TEMP DAY-SCHEDULES = ( "CHW-RESET-ASHRAE-DAY" ) .. "CHW-RESET-ASHRAE-SCH" = SCHEDULE-PD TYPE = RESET-TEMP MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "CHW-RESET-ASHRAE-WK" ) .. $ **************************************************************************** $ $ ASHRAE APP G/PRM DEFAULTS FOR LARGE CHW SYSTEM & CHILLERS $ $ ***************************************************************************** "CHW Loop Pump" = PUMP NUMBER = 1 MOTOR-CLASS = HI-EFF CAP-CTRL = VAR-SPEED-PUMP .. "CHW Primary Pump 1" = PUMP CAP-CTRL = ONE-SPEED-PUMP .. "CHW Primary Pump 2" = PUMP LIKE "CHW Primary Pump 1" .. "Chilled Water Loop" = CIRCULATION-LOOP TYPE = CHW LOOP-DESIGN-DT = 12 LOOP-OPERATION = DEMAND DESIGN-COOL-T = 44 COOL-SETPT-CTRL = OA-RESET MAX-RESET-T = 54 COOL-RESET-SCH = "CHW-RESET-ASHRAE-SCH" PIPE-HEAD = 26 LOOP-PUMP = "CHW Loop Pump" .. "Chiller-1" = CHILLER TYPE = ELEC-HERM-CENT CAPACITY-RATIO = 0.65 ELEC-INPUT-RATIO = 0.141 CHW-LOOP = "Chilled Water Loop" CHW-PUMP = "CHW Primary Pump 1" CONDENSER-TYPE = WATER-COOLED CW-LOOP = "Condenser Water Loop" CW-PUMP = "CW Pump 1" VARIABLE-SPEED = NO MIN-COND-T = 60 .. "Chiller-2" = CHILLER LIKE = "Chiller-1" CHW-PUMP = "CHW Primary Pump 2" CW-PUMP = "CW Pump 2" ..